LNG is transported as a liquid at about -162 C. At this temperature rubber hoses become brittle and crack, and carbon-steel pipes fail by low-temperature brittle fracture. Based on ISO 10380, ISO 16924 and GB 50156-2021, this article sets out the selection points for cryogenic hoses across materials, construction, thermal-shrinkage compensation, inspection and replacement, to help fueling stations reduce leakage and burst risks.
1. LNG cryogenic duty: -162 C is the dividing line for selection
- LNG is methane liquefied at about -162 C; GB/T 19204-2020 gives a boiling range of -166 C to -157 C and a density of 420-470 kg/m3.
- At low temperature carbon steel and ferritic and martensitic steels lose toughness and fracture brittly; only austenitic stainless steel gains better impact toughness at cryogenic temperature.
- The low-temperature impact test temperature for LNG austenitic stainless steel is -196 C, the same as the applicable temperature of cryogenic gaskets.
- Cooling the pipeline from ambient to -196 C shrinks austenitic stainless steel by about 3 mm per metre; a 10 m line shortens by about 30 mm, and this repeats at every pre-cooling cycle.
- LNG trapped between two valves vaporises and builds pressure rapidly on warming, so relief and process design must be considered together with hose selection.
2. Material selection: the boundary between austenitic stainless steel and PTFE lining
- The hose body should be 304L, 316L or 321 austenitic stainless steel, which keeps ductility and impact toughness at low temperature and is the mature material for cryogenic service.
- The annular bellows structure provides flexibility through corrugation geometry; the all-metal wall has zero gas permeation, suiting flammable volatile media such as LNG.
- A PTFE liner is not recommended for the LNG cryogenic body: PTFE is not a cryogenic structural material, and differential expansion between liner and metal is itself a failure source.
- Fitting seals may use metal-to-metal sealing or cryogenic-grade PTFE gaskets; this is a separate matter from body material selection and must not be confused.
- If the medium is changed to liquid oxygen, oxygen cleaning per CGA G-4.1 is required; ordinary metal hoses must not be substituted directly.
3. Construction selection: bellows, braid and end connections
- A typical build is an austenitic stainless-steel annular bellows core, an outer braid of the same grade stainless-steel wire, and welded or flanged ends.
- The braid carries the pressure load; pressure rating falls as diameter increases, so each specification must be checked case by case rather than covered by a single pressure value.
- EN ISO 10380 specifies a design factor for corrugated metal hoses typically of 4:1, with proof pressure about 1.5 times working pressure.
- Cold-end flanges and fittings must be the same grade austenitic stainless steel as the hose; carbon-steel flanges become brittle at low temperature and are a common hidden hazard.
- Vacuum-jacketed double-wall structures are a different product category; supply scope and certification must be confirmed separately and are not equivalent to ordinary cryogenic hoses.

4. Pressure, diameter, length and thermal-shrinkage compensation
- Fueling-station unloading hoses: design temperature not above -196 C, nominal pressure not less than twice the maximum working pressure of the loading and unloading system.
- Minimum burst pressure not less than 4 times nominal pressure; for a 1.6 MPa system, nominal pressure at least 3.2 MPa and burst at least 12.8 MPa.
- Unloading hose length should not exceed 6 m and must not be extended on site.
- LNG liquid transfer hoses commonly work at 30-50 bar, marine bunkering up to 50 bar, and dispenser hoses about 31-76 bar.
- Select diameter by flow: unloading DN50-DN200, marine bunkering DN100-DN250, dispensers commonly 1/2 in. to 1 in.
- Cut the hose to cold working length and include total line shrinkage in flexibility compensation; installation taut to ambient length is prohibited.
5. Safety accessories: breakaway valve, emergency shut-off and electrostatic grounding
- Fit a breakaway valve at the front or end of the hose; on external disconnection both ends separate fully and self-seal without visible leakage.
- Breakaway valve design pressure and design temperature must match the system and be included in periodic inspection.
- Provide anti-static grounding and a ground-status monitor at the unloading area; fixed grounding points should not be located in explosion-hazard Zone 1.
- LNG flowing at high speed in the hose builds static charge; hose body and fittings must remain electrically continuous and insulating sections are prohibited.
- Pipeline design should include safety valves and ventilation to prevent overpressure from re-warming vaporisation and the risk of cryogenic burns.
6. Inspection, proof test and replacement interval
- Visual check each shift: bulging, cracks, corrosion and fitting leakage; soap water may be used for leak detection.
- Loading and unloading hoses undergo one proof test per year at 1.5 times nominal pressure, with signed records retained.
- Broken inner wire layers and liner delamination cannot be detected while the exterior looks intact; only the proof test exposes them.
- General filling stations: replace every 2-3 years; high-frequency stations: every year; proof-test before re-commissioning after idle periods.
- Scrap immediately on hose bulging or cracking, fitting leakage or looseness, failed proof test or failed static continuity; do not continue using.
- Main standards include GB 50156-2021, the TSG R0005-2011 amendment, ISO 16924 and GB/T 20368-2021.
7. KUNGFLEX cryogenic fluid pipeline capability
- Can supply austenitic stainless-steel metal bellows cryogenic hose assemblies and matching fittings per ISO 10380 and ISO 16924.
- Provide 316L double ferrule, metal bellows and low-permeability hoses for hydrogen and cryogenic pipelines, with materials and seals selected by medium temperature.
- In-house 4000 kg, approx. 400 MPa burst test rig supports strength and reliability verification of assembly batches.
- Supply industrial fittings, quick couplings, ball valves and steel-tube assemblies, with complete piping packages by station duty.
- Products exported to 80+ countries, distributing Parker, Manuli, SPIR STAR and other brands, supporting supply to project standards.
Quick selection checklist
- [ ] Confirm medium temperature at LNG -162 C and low-temperature impact test at -196 C; no carbon or ferritic steel.
- [ ] Choose a 304L, 316L or 321 austenitic stainless-steel bellows body, all-metal zero permeation, no PTFE lining.
- [ ] Cold-end flanges and fittings in the same grade stainless steel; confirm EN ISO 10380 design factor 4:1 and proof pressure 1.5 times working pressure.
- [ ] Nominal pressure at least 2 times system maximum working pressure, burst at least 4 times nominal pressure, unloading hose length not over 6 m.
- [ ] Cut to cold length and include total line shrinkage; fit a breakaway valve and anti-static grounding.
- [ ] Annual proof test at 1.5 times nominal pressure with signed records retained; preventive replacement every 2-3 years.
About Shanghai Beirun Hydraulic Equipment Co., Ltd. (KUNGFLEX / Kongfu)
- Company: Shanghai Beirun Hydraulic Equipment Co., Ltd. (brand KUNGFLEX / Kongfu)
- 17 years in the industry, certified to ISO 9001:2015
- Authorized distributor for Gates; also distributes Parker, Manuli, SPIR STAR, Polyhose, ALFAGOMMA and Eaton
- In-house 4000 kg / approx. 400 MPa ultra-high-pressure burst test rig (about 10x the working pressure margin)
- Main products: hydraulic hose assemblies, industrial fittings, quick couplings, ball valves and steel-tube assemblies, plus SQ300 liquid-cooling connectors and hydrogen pipeline solutions
- Products exported to 80+ countries
- Hotline: 400-820-9728 / 13391148566
- Address: Room 101/201, Building 2, No. 4777 Jiasong North Road, Jiading District, Shanghai